MODEL NAME
|
TS650B
|
|
Topology
|
Line-Interactive
|
|
On-battery
Output Waveform
|
Simulated Sine Wave
|
|
INPUT
|
|
Maximum
Capacity
|
360W
|
|
Nominal
Input Voltage
|
110/120Vac or 220/230/240Vac
|
|
Nominal
Input Frequency
|
50Hz / 60Hz Auto Sensing
|
|
Input
Voltage Range
|
Rated Voltage +/- 25%
|
|
Input
Short Protection
|
Fuse
|
|
AC
Line-In Plug
|
110/120V
models
|
NEMA 5-15P
|

|
|
220/230/240V
models
|
Depends on local standards
|
|
OUTPUT
|
|
Nominal
Output Voltage
|
110/120Vac or 220/230/240Vac
|
|
Output
Voltage Regulation
|
Rated Voltage +/- 5%
|
|
Transfer
Time (Typical)
|
4 ms
|
|
Start
on Battery
|
Yes
|
|
Auto
Restart
|
Yes
|
|
Automatic
Voltage Regulator (AVR)
|
When the input voltage is 9 % to 25 % lower
than that of mains,
AVR raises the voltage by 15 % automatically.
|
|
When the input voltage is 9 % to 25 %
higher than that of mains,
AVR lowers the voltage by 13 % automatically.
|
|
Type
and Number of Outlets
|
110/120V
|
NEMA 5-15R
2 x Battery Backup
|

|
|
220/230/240V
|
IEC 320 C13
2 x Battery Backup
|

|
|
COMMUNICATIONS
INTERFACE
|
|
Communication
Port1)
|
RS232
|
|
Data
Line Surge Protection
|
RJ11 / RJ45
|
|
PROTECTION
|
|
Surge
Energy Rating
|
460 Joules (IEC outlets models)
265 Joules (NEMA outlets models)
|
|
Overload
Protection
|
UPS automatic shutdown if overload exceeds
110% from nominal UPS capacity over 60 seconds or 130% over 3 seconds.
|
|
Short
Circuit
|
UPS output immediate cut off or input fuse
protection
|
|
BATTERY
|
|
User
Replaceable Batteries
|
RBAT-1
|
|
Typical
Backup Time2)
|
21 minutes
|
|
Full
load runtime
|
2 minutes
|
|
Half
load runtime
|
9 minutes
|
|
Recharge
Time to 90%
|
< 4 hours
|
|
Protection
|
Auto discharge protection
|
|
ADVANCED
WARNINGS / DIAGNOSTICS
|
|
Front
Panel LEDs
|
Power Status / AC Mode / Battery Mode /
Battery Fault / Overload
|
|
Audible
Alarms
|
Battery Mode / Battery Low / Overload
|
|
ENVIRONMENTAL
PARAMETERS
|
|
Operating
Temperature
|
0˚~40˚C
/ 32˚~104˚F
|
|
Storage
Temperature
|
-20˚~60˚C / -4˚~140˚F
|
|
Audible Noise
|
<
40 dBA
|
|
PHYSICAL PARAMETERS
|
|
Dimensions (LxWxH):
|
Physical
|
12.5x3.8x5.3 inches / 320x97x135 mm
|
|
Weight
|
Net
|
6.5kg / 14.3lbs
|
|
Gross
|
7.0kg / 15.4lbs
|
|
CONFORMANCE
|
|
EMI/RFI
Compatibility
|
CE
|
|
Safety
Certifications
|
CE; UL
|
* Specifications are subject to change without notice.
1) Back-up time depends on the power consumption of the equipment attached to UPS and on battery capacity. Numbers herein are for reference only.
2) RS232 to USB adapter are available for purchase.